ControlLogix Architecture – Rockwell Automation

 In the last article, we discussed the most common type of PLC used in large-scale industries i.e. AB PLC (1756 ControlLogix).

ControlLogix Architecture

Today we will discuss about its architecture.


As seen in the picture, the control system consists of power supply modules, communication module, controller (1756-L55xx), redundancy module, ControlNet communication modules (1756-CNBR), remote IO modules & some other modules like flex IO & AC drive module.

As we are aware that a system has 2 controllers and the system we are talking about here also has 2 controllers installed in 2 different chassis. In the above picture, you can find the primary and secondary ControlLogix chassis.

The controller (CPU) can be identified by a key slot given on it. The CPU has 3 different modes like RUN, REMOTE RUN & PROGRAM.

Redundancy can be established through redundancy modules installed in both chassis connected through Fiber Optic cable. It is shown in the red color line in the above picture.
Once the redundancy modules in the redundant chassis pair are connected and powered, they determine which chassis is the primary chassis and which is the secondary chassis.

There are two PLC systems, we can simply call them PLC A and PLC B, or, chassis A and chassis B. We can also call them the primary controller (PLC A) and secondary controller (PLC B).

Either primary controller or secondary controller will be active and online for monitoring and controlling the plant. The other controller will be in standby mode. The other controller will be active if there is a problem with the primary controller.

If a switchover occurs, the new primary controller continues to execute programs, which begin with the highest-priority task that had been executed on the previous primary controller. The PLC’s switchovers occur as fast as 20 ms.

As we have seen controllers in redundancy, we can place the same IO modules in both chassis to make them redundant too.

Now the system we have taken has IO installed in the remote chassis. So here a 1756-CNBR card is installed in the main chassis and remote IO chassis so that they can communicate.

A redundant type connection or single connection can be used as per requirement (Here redundant is used). Remote IO chassis has separate power modules.

Similarly, different modules like flex IO & AC drive modules can be connected using ControlNet.

We can use Ethernet to communicate with server/HMI, although ControlNet can also be used. The advantage of Ethernet is high bandwidth i.e. 100 Mbps of 1 Gbps depending on the module used whereas ControlNet only gives 5 Mbps bandwidth.

Also, Ethernet is more preferred while having communication with other networks/systems. Other communication modes available are DeviceNet, DH+, DH485, Modbus & SynchLink.

The architecture we discussed is for a single controller used in a very small plant. But if the plant is big and has more areas then more controllers are required.

Also, a network of all controllers is also necessary to access them.


Now if the plant is large with many units in different physical areas and each having its own dedicated PLC, then the above-shown network can be made with the use of switches and Ethernet connection.

This was all about the architecture of AB PLC ControlLogix.

-END-


Comments

Popular posts from this blog

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

Thermowell Insertion and Immersion Length

 The thermowell is the industrial housing for temperature elements like RTD or thermocouple or temperature gauges. Thermowell is directly exposed to process fluid/media. Inside the thermowell, element/gauge is installed. Thermowell transfers the heat to the temperature element. Depending upon the element type, the fluid temperature can be known. So Thermowell protects the temperature element against harsh conditions and process fluid. It enables removal of the temperature element for replacement, repair, or testing without affecting the process system. Generally, thermowells are provided with all-temperature Elements like RTD or Thermocouple or temperature gauge. A few exceptions would be bearing RTD, skin type thermocouple, air duct thermometer, etc where thermowell is not applicable / required. When the thermowell assembly is inserted into the pipe, it is subjected to vibration. This vibration is caused by vortices to be generated alternately on either side of the thermowell. The...