Working Principle of Single Phase Preventer Relay

 In this post, we will learn the working principle of a single-phase preventer relay.


A three-phase supply drives the control components and field devices of an electrical panel. The controlling part is done by PLC.


As the outputs are controlled by PLC, if the three-phase supply fails, then there must be some means to protect the field devices from operating.


Table of contents

  • Single Phase Preventer Relay
  • Applications
  • Types
  • Working Principle

Because, if there is any phase failure and still the field device is operating, then it may damage it. If one supply fails, then still the field device like motor will continue to operate.


This will increase the load current in the remaining two phases and result in an unbalanced stator current. This can damage the motor windings.


Single Phase Preventer Relay

This protection can be done by a single-phase preventer relay. A single-phase preventer relay is a control device that detects any failure in phase supply and energizes its auxiliary relay contacts.


This contact is then given to the PLC which turns off its outputs through programming written.


Applications

Generally, this relay can be used to protect the circuit against the following types of failures –


  • over-voltage,
  • under-voltage,
  • over frequency,
  • under frequency,
  • asymmetry,
  • phase failure, etc.

Types

This relay works by two methods –


  1. current sensing and
  2. voltage sensing.
Both these types continuously monitor the phase sequence and if any failure occurs, then the internal trip circuit activates the relay contacts and sends a trip signal to the PLC.


Working Principle

Refer to the image (right-side) above for reference. It generally has 8 terminals. 3 terminals are for 3-phase supply, 2 terminals are for single-phase supply powering the relay device and 3 terminals are for auxiliary contacts.


The device has many settings for timers and other control parameters for accurately monitoring the phase sequence. The circuit inside continuously monitors the unbalance phase sequence or abnormal phase operation, and activates the relay output.


Corresponding logic is written in the PLC to sense the digital input given from this relay and turn off all the outputs. This will disconnect the motor or other field equipment from the three-phase supply and protect it from damage.


Practically, there are many causes that result in phase failure. Sometimes, the contactors of a motor may get open-circuited; or one of the fuses of any three-phase supply gets blown or melts; or the contactors are coated due to oxidation which will cause it to become non-conducting, etc.


In any case, the wrong phase supply can damage the windings of the motor and so, it is necessary to use this device to prevent any untoward incident.

Comments

Popular posts from this blog

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Dissolved Oxygen Analyzer Working Principle

 What is dissolved oxygen ? Dissolved oxygen refers to oxygen dissolved in water. Its concentration is expressed as the amount of oxygen per unit volume and the unit is mg/L. Biologically, oxygen is an essential element for respiration of underwater life and also acts as a chemical oxidizer. The solubility of oxygen in water is affected by water temperature, salinity, barometric pressure, etc. and decreases as water temperature rises. Measurement of dissolved oxygen by the membrane electrode method The membrane electrode method measures a diffusion current or reduction current generated by the concentration of dissolved oxygen or partial pressure of oxygen to obtain the concentration of dissolved oxygen. This method is not affected by the pH value of water being measured, oxidation and reduction substances, color, turbidity, etc. and the measurement method offers good reproducibility. When a sensor is inserted into water, an air layer forms on the membrane (Teflon membrane). The ox...