Pulse Timer Instruction in PLC Programming

 Let’s study the working of pulse timer instruction in Siemens PLC programming.


Pulse Timer in PLC

Block Description
Pulse Timer:
When Timer receives positive pulse at the set input (S), it enables the Q output as long as the preset value set for the timer. The signal change is necessary in order to enable the timer.

Timer will run as long as the input sign (S)  at “1” or accumulator value reaches preset value. The signal state at the output (Q) is at “1” as long as the timer is running. If input (S) changed from “1 to 0” before the time interval has elapsed, timer stopped along with disabling output (Q).

The timer reset input enables to reset the timer while it’s running. Accumulator value backs to zero. Accumulator value can be read at the BI and BCD output of the timer.

Pulse Extended Timer:
When Timer receives positive pulse at the set input (S), it enables the Q output as long as the preset value set for the timer. The signal change is necessary in order to enable the timer.

The signal state at the output (Q) is at “1” as long as the timer is running. If input (S) changed from “1 to 0” before the time interval has elapsed, timer continue to run and enables output (Q) till accumulator value reach preset value.

The timer reset input enables to reset the timer while it’s running. Accumulator value backs to zero. Accumulator value can be read at the BI and BCD output of the timer.

Ladder Logic
Case 1: When Input set (S) goes ON for the first time

Network 1:
Input I0.0 is pressed, it gives positive pulse to S input of timer (T0) which makes timer to start running upto 20s ,the time mentioned in the preset value(TV=ST#20s).Output (Q0.0) of timer (T0) enable for 20 s.

Network 2:
Input  I0.2 is pressed, it gives positive pulse to S input of timer (T1) which makes timer to start running upto 20s,the time mentioned in the preset value (TV=ST#20s).Output (Q0.1 )of timer (T1) enable for 20 s.
Case 2: When Input set (S) goes OFF before time interval (20s) get elapsed
Network 1:
Input (I0.0) to the timer (T0) is turned off before the time interval elapsed will make the timer to stop running and output (Q0.0) to go off.

Network 2:
Input (I0.2) to the timer (T1) is turned off before the time interval elapsed will make the timer to continue running and output (Q0.1) to remain ON till the time interval has elapsed.

Case 3: When Reset input (R) goes ON before time interval (20s) get elapsed
Network 1:
Reset Input (I0.1) to the timer (T0) is pressed; timer stopped running and disables the output (Q0.0).

Network 2:
Reset Input (I0.3) to the timer (T1) is pressed; timer stopped running and disables the output (Q0.1).


Comments

Popular posts from this blog

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

Thermowell Insertion and Immersion Length

 The thermowell is the industrial housing for temperature elements like RTD or thermocouple or temperature gauges. Thermowell is directly exposed to process fluid/media. Inside the thermowell, element/gauge is installed. Thermowell transfers the heat to the temperature element. Depending upon the element type, the fluid temperature can be known. So Thermowell protects the temperature element against harsh conditions and process fluid. It enables removal of the temperature element for replacement, repair, or testing without affecting the process system. Generally, thermowells are provided with all-temperature Elements like RTD or Thermocouple or temperature gauge. A few exceptions would be bearing RTD, skin type thermocouple, air duct thermometer, etc where thermowell is not applicable / required. When the thermowell assembly is inserted into the pipe, it is subjected to vibration. This vibration is caused by vortices to be generated alternately on either side of the thermowell. The...