How to Install GSD File in Step 7 PLC using Simatic Manager?

 First, before going through installing a GSD file, let’s understand what GSD file is and why we require to install them in the software.

For example, we have a flow transmitter that has a function like flow totalizer. The transmitter will store the flow rate, totalizer value, and flow units. The transmitter is also capable of remote configuration from the PLC’s. It will accept the totalizer reset command, sending the flow parameters to PLC.

The PLC can be communicated with flow transmitters only when it knows where to communicate, which addresses the flow transmitter data is available. The transmitters will be provided with a GSD file from the manufacturer which contains all the addresses where the flow parameters will be available.

In such a case, GSD means General Station Definition which contains a form of the text which interprets by PLC which then converts it into proper command form.

In short, we can say that the GSD file gives an identity of devices commands, and parameters.

Another thing also you can note that the GSD file contains the description of the Profibus or Profinet’s description.

Install GSD File in Step 7 PLC

Let’s dig into installing the procedure of the GSD file in step 7 for all the versions.

Step 1:

Open Simatic manager and open any existing project or create a new one.

Step 2:

To update the GSD file, we have to update the hardware as shown in the below window.

Step 3:
Double click on hardware will open up module set up window. After opening the following window click on “option” and open “Install GSD file” option.

Step 4:
Following window will pop-up. To add particular GSD file as per our application, we have to download it from the internet or manufactures will be provided you a CD.

Step 5:
GSD file is provided by the manufacturer or you can download it by doing a google search.

Step 6:
To add GSD file as shown in the above window, browse it and add that downloaded file.

Step 7:
Click “install” to install the GSD file.

Step 8:
After adding the file you can find it as shown in below window. Here, expand Profibus-DP and or directly write in search of the file which you have downloaded.


Step 9:
Add that module by dragging onto the Profibus network. Do setting as per your application.

END


Comments

Popular posts from this blog

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Dissolved Oxygen Analyzer Working Principle

 What is dissolved oxygen ? Dissolved oxygen refers to oxygen dissolved in water. Its concentration is expressed as the amount of oxygen per unit volume and the unit is mg/L. Biologically, oxygen is an essential element for respiration of underwater life and also acts as a chemical oxidizer. The solubility of oxygen in water is affected by water temperature, salinity, barometric pressure, etc. and decreases as water temperature rises. Measurement of dissolved oxygen by the membrane electrode method The membrane electrode method measures a diffusion current or reduction current generated by the concentration of dissolved oxygen or partial pressure of oxygen to obtain the concentration of dissolved oxygen. This method is not affected by the pH value of water being measured, oxidation and reduction substances, color, turbidity, etc. and the measurement method offers good reproducibility. When a sensor is inserted into water, an air layer forms on the membrane (Teflon membrane). The ox...