Compare Online and Offline PLC Programs

 This article is about to compare online and offline PLC programs using the Siemens TIA Portal.

Online and Offline PLC Programs

Offline program means the program which resides in the PC or laptop and online program means the program which resides in the PLC.

To understand the comparison between online and offline programs, I have created one FC block and one OB block example logic.

Follow the below steps to do the comparison of these programs.

Step 1:

Open TIA Portal. Open an existing program.

Here, I have chosen an example of a PLC program that is used to turn ON eight outputs by pressing the START button.

In the second Network, I have used the FC block.

Some times we make some changes in the PLC programs but may forget to download the modified logic to the PLC. After some time, if we didn’t recall the modified logic in our PC or laptop then there will be different programs in PLC and PC. So to identify the modified logic we can compare offline (PC) and online (PLC) programs to identify the modified logic.

Step 2:
As you can see in the below program, I have downloaded both networks into the PLC.

Assume the second line in the first network is not downloaded to the PLC.

Step 3:
To compare online and offline plc programs, do follow the steps as shown in the below window.

Right-click on the CPU, go to Compare and select offline/online option in the drop-down
Step 4:
The following split window will open up.

Here, on the left side you can see an offline program and on the right side is an online program.
As you can see, if logic is different between offline and online programs then it will indicate in different colors.
Green color shows that both offline and online programs are identical.

A combination of blue and orange shows that blocks are not identical and further investigation is required.

Step 5:
To know the reason, do right click on OB and click on “start detailed comparison” as shown in the below window.

Step 6:
Here, a comparison window will open up.

Clicking on a detailed comparison will take you to the program where the logic is modified.

Some issues with the first network, as it displays a blue and orange icon.

As you can see in the first network, offline program on the left-hand side contain one extra line of the logic.

The second network is fine as you can see the green button in front of that network.

Step 7:
Do follow the same step as above to check all the conflicts.

You can download the blocks whose logic is to be modified in the PLC

After downloading the program to the PLC, once again do the comparison.

In the below window you can see that there are no differences between offline and offline programs, so it displays green color buttons.

This is how you can check the conflicts between offline and online programs.

Note: Some times there will be faults also appear due to these differences.





Comments

Popular posts from this blog

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

The Method and Process of Siemens PLC Hardware Configuration

 The hardware configuration of Siemens PLC can usually adopt the following methods and processes: Determine control tasks and system requirements: Before hardware configuration, it is necessary to clarify the tasks and requirements of the control system, including the requirements for input and output points, control accuracy, speed, and safety. Select the PLC model and module: According to the control task and requirements, select the appropriate PLC model and module, including CPU, I/O module, communication module, power supply module, etc. Assemble the cabinet and install the modules: According to the selected PLC model and module, assemble the cabinet and install the modules, pay attention to the installation sequence, cable wiring, wiring method, etc. Connect the input and output devices: connect the input and output devices with the input and output modules of the PLC, you need to pay attention to the correctness, stability and safety of the wiring. Perform software configura...