Skip to main content

Types of Level Measurement

 Types of Level Measurement

Two methods used to measure level;

Direct or Mechanical method, and

Indirect or Inferential methods.

1. Mechanical or Direct Method

Direct level measurement is simple, almost straightforward and economical; it uses a direct measurement of the distance (usually height) from the datum line, and used primarily for local indication. It is not easily adopted to signal transmission techniques for remote indication or control.

a. Dip Sticks and Lead Lines

Flexible lines fitted with end weights called chains or lead lines have been used for centuries by seafaring men to gauge the depth of water under their ships. Steel tape having plump bob – like weights, and stored conveniently in a reel are still used extensively for measuring level in fuel oil bunkers and petroleum storage tanks. (see figures below)

Though crude as this methods seems, it is accurate to about 0.1% with ranges up to about 20 feet.

Although the dipstick and lead line method of level measurement are unrivalled in accuracy, reliability, and dependability, there are drawbacks to this technique.

First, it requires an action to be performed, thus causing the operator to interrupt his duty to carry out this measurement. There cannot be a continuous representation of the process measurement.

Another limitation to this measuring principle is the inability to successfully and conveniently measures level values in pressurised vessels. These disadvantages limit the effectiveness of these means of visual level measurement.

b. Sight Glass
Another simple method is called sight glass (or level glass). It is quite straightforward in use; the level in the glass seeks the same position as the level in the tanks. It provides a continuous visual indication of liquid level in a process vessel or a small tank and are more convenient than dip stick, dip rod and manual gauging tapes.
Sight glass A is more suitable for gauging an open tank. A metal ball normal used in the tube to prevent the fluid from flowing out of the gauge. Tubular glass of this sort is available in lengths up to 70 inches and for pressure up to 600 psi. It is now seldom used.

The closed tank sight glass B, sometimes called a ‘reflex glass’, is used in many pressurized and atmospheric processes. The greatest use is in pressurised vessel such as boiler drums, evaporators, condensers, stills, tanks, distillation columns, and other such applications. The length of reflex glass gauges ranges from a few inches or eight feet, but like the tube type gauges, they can be gauge together to provide nearly any length of level measurement.

The simplicity and reliability of gauge type level measurement results in the use of such devices for local indication. When level transmitters fail or must be out of service for maintenance, or during times of power failure, this method allow the process be measured and controlled by manual means.

However, glass elements can get dirty and are susceptible to breakage thus presenting a safety hazard especially when hot, corrosive or flammable liquids are being handled.

c. Chain or Float Gauge
The visual means of level measurement previously discussed are rivaled in simplicity and dependability by float type measurement devices. Many forms of float type instruments are available, but each uses the principle of a buoyant element that floats on the surface of the liquid and changes position as the liquid level varies.

Many methods have been used to give an indication of level from a float position with the most common being a float and cable arrangement. The operational concept of a float and cable is shown in the following diagram;
The float is connected to a pulley by a chain or a flexible cable and the rotating member of the pulley is in turn connected to an indicating device with measurement graduation. As can be seen, as the float moves upward, the counterweight keeps the cable tight and the indicator moves along the circular scale.

B. Inferential or Indirect Methods
Indirect or inferred methods of level measurement depend on the material having a physical property which can be measured and related to level. Many physical and electrical properties have been used for this purpose and are well suited to producing proportional output signals for remote transmission. This method employs even the very latest technology in its measurement.

Included in these methods are;

A. Buoyancy :-
the force produced by a submerged body which is equal to the weight of the fluid it displaces.

B. Hydrostatic head :-
the force or weight produced by the height of the liquid.

C. Sonar or ultrasonic :-
materials to be measured reflect or affect in a detectable manner high frequency sound signals generated at appropriate locations near the measured material.

D. Microwave :-
similar to ultrasonic but uses microwave instead of ultrasonic beam.

E. Conductance :-
at desired points of level detection, the material to be measured conducts (or ceases to conduct) electricity between two fixed probe locations or between a probe and vessel wall.

F. Capacitance :-
the material to be measured serves as a variable dielectric between two fixed capacitor plates. In reality, there are two substances which form the dielectric -the material whose measurement is desired and the vapor space above it.

The total dielectric value change as the amount of one material increases while the other decreases.

G. Radiation :-
the material measured absorbs radiated energy. As in the capacitance method, vapor space above the measured material also has an absorbing characteristics, but the difference in absorption between the two is great enough that the measurement can be related quite accurately to measured material.

H. Weight: :-
the force due to weight can be related very closely to level when its density is constant. Variable concentrations components or temperature variations present difficulties, however.

I. Resistance :-
Pressure of the measured material squeezes two narrowly separated conductor together, reducing overall circuit resistance in an amount proportional to level.

J. Micro-Impulse :-
“time-of-flight”, electrical pulses launch and travels back in frequency directly proportional to the level of the liquid.

Article Source : N. Asyiddin


Comments

  1. Your blog is very valuable which you have shared here about sight glass. I appreciate your efforts which you have put into this article and also it is a gainful article for us. Thank you for sharing this article here.
    sight glass

    ReplyDelete

Post a Comment

Popular posts from this blog

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Thermowell Insertion and Immersion Length

 The thermowell is the industrial housing for temperature elements like RTD or thermocouple or temperature gauges. Thermowell is directly exposed to process fluid/media. Inside the thermowell, element/gauge is installed. Thermowell transfers the heat to the temperature element. Depending upon the element type, the fluid temperature can be known. So Thermowell protects the temperature element against harsh conditions and process fluid. It enables removal of the temperature element for replacement, repair, or testing without affecting the process system. Generally, thermowells are provided with all-temperature Elements like RTD or Thermocouple or temperature gauge. A few exceptions would be bearing RTD, skin type thermocouple, air duct thermometer, etc where thermowell is not applicable / required. When the thermowell assembly is inserted into the pipe, it is subjected to vibration. This vibration is caused by vortices to be generated alternately on either side of the thermowell. The...