Impulse Piping standards for Field instruments

What is Impulse Piping?

The impulse piping is the one which connects the process outputs to the transmitter.

It must convey the process pressure accurately. If for example, the gas collects in a liquid-filled impulse line, or the drain of a gas-filled impulse line becomes plugged, it will not convey the pressure accurately.

Since this will cause errors in measurement output, selecting the proper piping method for the process fluid (gas, liquid or steam) is very important. We discuss below some of the most common routing principles for impulse piping.

Differential Pressure Transmitters Hook up
In differential pressure transmitters, there is a chance that process fluid (liquid, gas or vapors) may accumulate inside the impulse piping that can cause inaccurate reading of pressures.

There are three cases as depicted by the figure.

1. Liquid
If the process fluid is liquid, the transmitter should be placed lower than the taps.

2. Gas
If the process fluid is gas, the transmitter should be placed higher than the taps.

3. Steam
If the process fluid is steam, it has more chances to vaporize, so we should use condensate pot and the transmitter should be placed at lower level than the taps.

Summary :
Liquid lines :
On liquid lines the transmitter is mounted below the orifice plate because liquids have a property of self draining.

Gas Service :
On gas service the transmitter is mounted above the orifice plate because Gases have a property of self venting and secondly condensate formation.

Steam Service :
On steam service the transmitter is mounted below the orifice plate with condensate pots. The pots should be at the same level.






 

Comments

Popular posts from this blog

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Dissolved Oxygen Analyzer Working Principle

 What is dissolved oxygen ? Dissolved oxygen refers to oxygen dissolved in water. Its concentration is expressed as the amount of oxygen per unit volume and the unit is mg/L. Biologically, oxygen is an essential element for respiration of underwater life and also acts as a chemical oxidizer. The solubility of oxygen in water is affected by water temperature, salinity, barometric pressure, etc. and decreases as water temperature rises. Measurement of dissolved oxygen by the membrane electrode method The membrane electrode method measures a diffusion current or reduction current generated by the concentration of dissolved oxygen or partial pressure of oxygen to obtain the concentration of dissolved oxygen. This method is not affected by the pH value of water being measured, oxidation and reduction substances, color, turbidity, etc. and the measurement method offers good reproducibility. When a sensor is inserted into water, an air layer forms on the membrane (Teflon membrane). The ox...