DP Diaphragm Capillary Seal Level instrument Calibration Procedure

 How to calibrate the level instrument with DP type Capillary Seal sensors

The use of capillary with fluid inside will the make us to have nice and careful calculation to find what is the range between 0% – 100%. Below is some examples how to find calibrated range for many possible position of the DP type Capillary Seal Level transmitter.

The information given is: H = 100 Inch (Center to Center), Process SG Liquid = 1, h = 50 Inch, SG fill fluid = 1.2. What is the calibrated range? what is the required URV and LRV? for cases below:

1. The first case (atmospheric) is as follows:

To find a range of 0% -100% level of process fluid with DP Type Level value corresponding instrument is as follows:

0% -> Under these conditions the fill fluid in the capillary has put pressure on the sensor even though the tank is empty. DP received by the sensor is equal to or 50 h InFillFluid InFillFluid which has SG = 1.2. To make it dimensionless InH2O then 50 InFillFluid converted = 50 x 1.2 = 60 InH2O.

100% -> In this condition experienced DP sensor is of (process fluid) + (fill fluid). The pressure sensor is received (100 InH2O) + (60 InH2O) = 160 InH2O.

Calibrated range is 60 InH2O to 160 InH2O.

2. The second case (atmospheric) is as follows:
To find a range of 0% -100% level of process fluid with DP Type Level value corresponding instrument is as follows:

0% -> Under conditions of process liquid tank is empty, the sensor will receive the DP negative because it is higher than the tapping point kapilary (Zero Elevation). Is this a vacuum condition because of pressure disuck or aspirated? I do not think so. DP nagative as head h and the level of process liquid H will push each other in opposite directions. The higher level of process liquid, the higher the pressure that is otherwise against the head h. H Head pressure is 50 InFillFluid = 60 InH2O but negative or – 60 InH2O.

100% -> In this condition experienced DP sensor is on the process pressure fluid- pressure fluid fill. The pressure sensor is received (100 InH2O) – (60 InH2O) = 40 InH2O.

InH2O calibrated range is -60 to 40 InH2O.

3. The case of the third (closed tank roof) is as follows:

To find a range of 0% -100% level of process fluid with DP Type Level value corresponding instrument is as follows:

0% -> Under these conditions the fill fluid in the capillary has put pressure on the sensor from both sides even though the tank is empty. Pressure received by the sensors of Hi -side (tapping point below) amounted h InFillFluid or 50 InFillFluid which has SG = 1.2. To make it dimensionless InH2O then 50 InFillFluid converted into 50 x 1.2 = 60 InH2O of the Hi-side. Lo received pressure sensor -side(tapping point above) is equal to H + h InFillFluid or 150 InFillFluid which has SG = 1.2. To make it dimensionless InH2O then 150 InFillFluid converted into 150 x 1.2 = 180 InH2O. Wah both sides put pressure yes yes although the tank is empty? DP when the level of 0% is obtained by subtracting the pressure (Hi-side) – (Lo-side). Level 0% = (60 InH2O) – (180 InH2O) = – 120 InH2O. You know if, in the tank already contained gas or vapor then with the Hi and Lo-side tapping point then by subtracting each method (remember DP = difference) is the pressure of gas / vapor on the surface of the liquid will cancel out all by itself.

100% -> In this condition experienced DP sensor is of (process fluid pressure) + (Hi fill fluid pressure) – (Lo pressure fluid fill). DP received sensor is (100 InH2O) + (60 InH2O) – (180 InH2O) = -20 InH2O. Gas or Vapor pressure above the liquid does not need to be taken into account because it will cancel out the Hi and Lo side by itself.

Range is calibrated -120 to -20 InH2O InH2O.

4. The case of the four (closed tank roof) is as follows:
To find a range of 0% -100% level of process fluid with DP Type Level value corresponding instrument is as follows:

0% -> Under these conditions the fill fluid in the capillary has put pressure on the sensor from both sides even though the tank is empty. Pressure received by the sensors of Hi -side (tapping point below) amounted h InFillFluid or 50 InFillFluid which has SG = 1.2, but negative. To make it dimensionless InH2O then converted InFillFluid -50 to -50 x 1.2 = – 60 InH2O of the Hi-side. Lo received pressure sensor -side (tapping point above) amounted Hh InFillFluid or 50 InFillFluid which has SG = 1.2. To make it dimensionless InH2O then 50 InFillFluid converted into 50 x 1.2 = 60 InH2O. Wah both sides put pressure yes yes although the tank is empty? DP when the level of 0% is obtained by subtracting the pressure (Hi-side) – (Lo-side). DP on Level 0% = (-60 InH2O) – (60 InH2O) = – 120 InH2O. You know if, in the tank already contained gas or vapor then with the Hi and Lo-side tapping point then by subtracting each method (remember DP = difference) is the pressure of gas / vapor on the surface of the liquid will cancel out all by itself.

100% -> In this condition experienced DP sensor is on (pressure process fluid) – (Hi fill fluid pressure) – (Lo pressure fluid fill). DP received sensor is (100 InH2O) – (60 InH2O) – (60 InH2O) = -20InH2O. Gas or Vapor pressure above the liquid does not need to be taken into account because it will cancel out the Hi and Lo side by itself.

Range is calibrated -120 to -20 InH2O InH2O.






Comments

Popular posts from this blog

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Dissolved Oxygen Analyzer Working Principle

 What is dissolved oxygen ? Dissolved oxygen refers to oxygen dissolved in water. Its concentration is expressed as the amount of oxygen per unit volume and the unit is mg/L. Biologically, oxygen is an essential element for respiration of underwater life and also acts as a chemical oxidizer. The solubility of oxygen in water is affected by water temperature, salinity, barometric pressure, etc. and decreases as water temperature rises. Measurement of dissolved oxygen by the membrane electrode method The membrane electrode method measures a diffusion current or reduction current generated by the concentration of dissolved oxygen or partial pressure of oxygen to obtain the concentration of dissolved oxygen. This method is not affected by the pH value of water being measured, oxidation and reduction substances, color, turbidity, etc. and the measurement method offers good reproducibility. When a sensor is inserted into water, an air layer forms on the membrane (Teflon membrane). The ox...