Calibrating Level Transmitter with Remote Seals

 How to calibrate the transmitter with a remote seal differential which is implemented in level measurement.Actually, not like where I calibrate the detailed step by step (usually with a HART Communicator), which will be discussed in this post is how to determine the calibration parameters, so that the transmitter works on a range that we want according to the process conditions. But, prior to the calculation method determines the LRV and URV, let us recognize the term first.

There are two terms commonly used in the calibration of the level transmitter with differential transmitter:

Zero Suppression

Zero suppressed required if the transmitter pressure gauge or absolute installed under tapping the side of the high pressure (the bottom side of the process connection). If the transmitter is mounted below the tapping side of the high pressure, the liquid filler (fill fluid) in the capillary puts pressure on the sensor transmitter so as to provide a positive pressure reading even if the tank is empty.

Zero Elevation

Instead, Elevated Zero is required if the pressure gauge or absolute transmitter mounted above the high pressure tapping side (bottom side of the process connection) or on the application of the twoseal differential transmitter (low side and high side). In this case, the transmitter reads a negative pressure when the tank is empty though. This is caused by the effect of head pressure on the fluid filler (fill fluid) on the remote seal capillary tube.

1. Suppressed Zero

Calibrating Transmitter System One Seal with suppressed Zero done if the transmitter is installed below the tapping point the high pressure side as shown below

From the picture above, it is known an open tank level is measured by a level transmitter that uses a single remote seal.

(s f) = specific gravity of the fill fluid (liquid filler in the capillary of remote seal)

(h) = the distance between the process of tapping points to the transmitter.

(s p) = specific gravity of process media that are in the tank.

(H) = The range of levels to be measured.

step 1

Calculate the amount of zero suppression by multiplying the distance between the process connection and the transmitter (h) by gravity liquid filler specifiec remote regret (s f):

Zero Suppression = (h) (s f) = (40 in) (0.93 INH 2 O / in) = 37.2 INH 2 O

Step 2

Calculate the span by multiplying the level range to be measured (H) by the specific gravity of the media that are in the process tanki.specific gravity (s p):

Span = (H) (s p) = (120 in) (1.2 INH 2 O / in) = 144 INH 2 O

Step 3

Determine / calculate calibration for the transmitter, which results in step 1 (zero suppression) as the LRV (Lower Range Value) and results in step 1 plus results in step 2 as the URV (Upper Range Value.

Calibration = “Zero Suppression” until (“Zero Suppression” + “Span”)

= 37.2 INH 2 O to (37.2 + 144) INH 2 O

INH 2 O = 37.2 to 181.2 INH 2 O

Conclusion

So, we calibrate the transmitter with:

LRV = 37.2 INH 2 O

URV = 181.2 INH 2 O

2. Elevated Zero – Open tank
Calibration is performed if the transmitter is mounted above (higher than) the high side tap
Is known:

(s f) = 1.9 in H 2 O / inch

(h) = -30 inches

(s p) = 1.1 in H 2 O / inch

(H) = 120 inches

From the picture above, it is known an open tank level measured her with a transmitter that uses a single remote seal with a transmitter is placed on the high side tapping point.
(s f) = specific gravity of the fill fluid (liquid filler in the capillary of remote seal)

(h) = the distance between the process of tapping points to the transmitter (note the minus sign).

(s p) = specific gravity of process media that are in the tank.

(H) = The range of levels to be measured.

step 1

Calculate the amount of zero elevation by multiplying the distance between the process connection and the transmitter (h) by the specific gravity liquid filler remote regret (s f):

Zero Suppression = (h) (s f) = (-30 in) (1.9 INH 2 O / in) = -57 INH 2 O

Step 2

Calculate the span by multiplying the level range to be measured (H) by the specific gravity of the process media are in the tank, pecific gravity (s p):

Span = (H) (s p) = (120 in) (1.1 INH 2 O / in) = 132 INH 2 O

Step 3

Determine / calculate calibration for the transmitter, which results in step 1 (zero elevation) as the LRV (Lower Range Value) and results in step 1 plus results in step 2 as the URV (Upper Range Value).

Calibration = “Elevation Zero” until (“ZeroElevation” + “Span”)

= -57 INH 2 O to (-57 + 132) INH 2 O

= -57 INH 2 O to 75 INH 2 O

Conclusion

So, we calibrate the transmitter with:

LRV = -57 INH 2 O

URV = 75 INH 2 O

3. Elevated Zero – Closed Tank
This calibration is done if a transmitter with two seal system installed one tapping point level with or above or below the high pressure tap side.

Is known:

(Sf) = 1:07 in H2O / inch

(h) = – 400 inches

(Sp) = 0.9 in H2O / inch

(H) = 350 inches

From the picture above, it is known an open tank level measured her with a transmitter that uses two remote seals each for high and low pressure side of his, the transmitter is placed under the high side tapping point.

(s f) = specific gravity of the fill fluid (liquid filler in the capillary of remote seal)

(h) = the distance between the process of tapping points to the transmitter (note the minus sign).

(s p) = specific gravity of process media that are in the tank.

(H) = The range of levels to be measured.

step 1

Calculate the amount of zero elevation by multiplying the distance between the process connection and the transmitter (h) by gravity liquid filler specifiec remote regret (s f):

Zero Elevation = – (h) (s f) = – (400 in) (1:07 INH 2 O / in) = -428 INH 2 O

Step 2

Calculate the span by multiplying the maximum height of the process fluid (H) by the specific gravity of the process media are in the tank, specific gravity (s p):

Span = (H) (s p) = (350 in) (0.9 INH 2 O / in) = 315 INH 2 O

Step 3

Determine / calculate calibration for the transmitter, which results in step 1 (zero elevation) as the LRV (Lower Range Value) and results in step 1 plus results in step 2 as the URV (Upper Range Value).

Calibration = “Elevation Zero” until (“Elevation Zero” + “Span”)

= -428 INH 2 O until the (-428 + 315) INH 2 O

= -428 To -113 INH INH 2 O 2 O

Conclusion

So, we calibrate the transmitter with:

LRV = -428 INH 2 O

URV = -113 INH 2 O




Comments

Popular posts from this blog

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Dissolved Oxygen Analyzer Working Principle

 What is dissolved oxygen ? Dissolved oxygen refers to oxygen dissolved in water. Its concentration is expressed as the amount of oxygen per unit volume and the unit is mg/L. Biologically, oxygen is an essential element for respiration of underwater life and also acts as a chemical oxidizer. The solubility of oxygen in water is affected by water temperature, salinity, barometric pressure, etc. and decreases as water temperature rises. Measurement of dissolved oxygen by the membrane electrode method The membrane electrode method measures a diffusion current or reduction current generated by the concentration of dissolved oxygen or partial pressure of oxygen to obtain the concentration of dissolved oxygen. This method is not affected by the pH value of water being measured, oxidation and reduction substances, color, turbidity, etc. and the measurement method offers good reproducibility. When a sensor is inserted into water, an air layer forms on the membrane (Teflon membrane). The ox...