Skip to main content

Thermocouple Details

 Thermocouple wiring

  • The thermocouple extension wire should meet the requirements of ISA/ANSI MC96.1 or IEC-60584.
  • Thermocouple signals are low-level signals that should be properly shielded and grounded to prevent noise interference with the signal.
  • Insulated hot junctions shall have an insulation resistance to ground of 50 megohms minimum at ambient temperature and 2 megohms minimum at 4508C (8508F).
  • Terminals within the head shall be clearly marked ‘+’, ‘-’, ‘ground’, as appropriate.
  • The multi circuits within heads shall be clearly identified
  • Check that the polarity and continuity of the lead wires are consistent through all the junction boxes from the thermocouple head to the control center

Grounded Thermocouple

  • For grounded thermocouples, check that the shield wire is terminated at the grounded thermocouple head in accordance with the manufacturer’s instructions and not at the shield connection on the control center or instrument terminals

Un-Grounded Thermocouple
  • For ungrounded thermocouples, check that the shield wire is terminated in the control room.
  • Grounding of the shield at more than one location should be avoided. Individual shielding of multi-pair cables, in addition to an overall shield, can help maintain the shield circuit at the individual ground potential all the way back to the receiver location.
Notes
  • Thermocouples can be tested by immersion in a temperature bath and the output measured using a Portable Calibrator.
  • Thermocouple selection is done based on temperature range and accuracy as per ISA/ANSI/IEC standards.
Thermocouple Color Codes

Image Courtesy: Omega
Thermocouple Tolerance
1) Tolerance is referred to as the maximum allowable deviation between hot junction temperature and the temperature derived from the EMF table.

2) ASTM temperature is C or % value for the measured temperature, which is greater.

3) | t | is the measuring temperature indicated by the temperature irrelevant to the symbol + or -.

4) Class 1, 2, or 3 conforms to the old JIS Class 0.4, 0.75 or 1.5, respectively.

5) JIS Standard is identical with IEC, BS or DIN Standard except for a part.

6) The tolerance of JISC1605 and JISC1602 is completely the same.

7) ASTM Standard is same as the old ANSI Standard.

8) Tolerances given in this table apply only to new wire as delivered to the user and do not allow for changes in characteristics with use. (ASTM E230)

9) The standard tolerances shown do not apply to Type E mineral-insulated, metal-sheathed (MIMS) thermocouples and thermocouple cables as described in Specifications E608/E608M and E585/E585M. The standard tolerances for MIMS Type E constructions are the greater of 2.2°C or 0.75 % from 0 to 870°C and the greater of 2.2°C or 2 % from -200 to 0°C.
Thermocouple Standard



Thermocouple Troubleshooting
Reference: okazaki



Comments

Popular posts from this blog

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

Thermowell Insertion and Immersion Length

 The thermowell is the industrial housing for temperature elements like RTD or thermocouple or temperature gauges. Thermowell is directly exposed to process fluid/media. Inside the thermowell, element/gauge is installed. Thermowell transfers the heat to the temperature element. Depending upon the element type, the fluid temperature can be known. So Thermowell protects the temperature element against harsh conditions and process fluid. It enables removal of the temperature element for replacement, repair, or testing without affecting the process system. Generally, thermowells are provided with all-temperature Elements like RTD or Thermocouple or temperature gauge. A few exceptions would be bearing RTD, skin type thermocouple, air duct thermometer, etc where thermowell is not applicable / required. When the thermowell assembly is inserted into the pipe, it is subjected to vibration. This vibration is caused by vortices to be generated alternately on either side of the thermowell. The...