Skip to main content

Instrumentation Engineer’s Calibration Mistakes

 Instrumentation Engineer’s Calibration Mistakes

Error When Attempting to Reverse the Range

In some applications, particularly DP level, it is necessary to reverse the range such that the LRV > URV.


For instance, the range may have been set -87 to -1 mbar initially, but the application may actually require the range to be -1 to -87 mbar. That is the range has to be reversed:


Before :


LRV = -87 mbar  &  URV = -1 mbar


After Change :


LRV = -1 mbar  &  URV = -87 mbar


To make this range change the technician would typically make the mistake of directly enter -1 mbar for LRV which would be rejected since both URV and LRV would then be -1 mbar leaving a span of 0 mbar which would violate the minimum span.


Or, the technician would attempt to directly enter -87 mbar for URV which would also be rejected since both URV and LRV would then be – 87 mbar also violating the minimum span.


The solution is to first enter an intermediate value. For instance, setting the LRV to -40, then setting URV to -87, and lastly setting LRV to the final -1 mbar.


The same procedure applies if the sensor trim points are to be reversed.


4-20 mA Range Mismatch 

If the range set in the transmitter does not match the range in the DCS, alarms, controls, and indication will not function correctly.


Therefore it is important to document any range changes such that the correct range is set when transmitters are replaced.



In this above example a mismatch in LRV results in erroneous indication.


Corrupting the range to make 4-20 mA right

Don’t use range setting to correct a sensor error. For example, a 4-20 mA/HART pressure transmitter ranged 0 to 100 inH2O may due to mounting position get a shift in reading of 1 inH2O.



 

The analog output will be 4.16 mA when no pressure is applied, making the field indicator or HMI show 1 inH2O.


A common mistake is to isolate, equalize, and vent the manifold and click the ‘Set PV LRV’ command in the device management software or handheld field communicator, or pushing the ‘zero’ and button on the device thus changing the range bringing the analog output to 4 mA.


However, checking the PV in the device management software or local transmitter indicator will reveal the sensor reading with no pressure applied is still 1 inH2O and the range is changed to 1 to 101 in H2O. Two wrongs appear to make a right.


The correct way to correct for shift or drift is to do a sensor trim.


Corrupting the sensor reading to make 4-20 mA right

Don’t use sensor trim to cancel a wet-leg. For example, a 4-20 mA/HART pressure transmitter ranged 0 to 100 inH2O may when mounted below the tank read 1 inH2O.


The analog output will be 4.16 mA when the level is zero (at the tank datum point), making the field indicator or HMI show 1 inH2O.


A common mistake is to click the ‘Zero Trim’ command in the device management software or handheld field communicator thus changing the sensor reading bringing the analog output to 4 mA.


However, if the 4-20 mA/HART pressure transmitter is isolated and vented, and the PV checked in the device management software or local transmitter indicator, it will show the sensor reading with no pressure applied is -1 inH2O. Two wrongs appear to make a right.


The correct way to cancel a wet leg is to set the range.


Non-interactive zero and span

One of the major time saving benefits that came with microprocessor-based transmitters was non-interactive zero and span:


When lower range value is set to applied input, the span (i.e. the difference between upper range value and lower range value) is maintained. That is, the upper range value is shifted by the same amount as the lower range value.


For instance, if the original range was 0-100 kPa, and lower range value is set to applied input when the applied input is 20 kPa, the new range will be 20-120 kPa, maintaining the original span of 100 kPa.


That is, the upper range value was also shifted by 20 kPa just like the lower range value.


However, if upper range value is set to applied input, the lower range value zero) is not changed.


For instance, if the original range was 0-100 kPa, and upper range value is set to applied input when the applied pressure is 80 kPa, the new range will be 0-80 kPa, maintaining the original zero of 0 kPa. That is, the lower range value was not shifted.


That is, changing the zero does not affect the span, changing the span does not affect the zero. This is non-interactive zero and span.


Article Source : Eddl


 


Comments

Popular posts from this blog

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Dissolved Oxygen Analyzer Working Principle

 What is dissolved oxygen ? Dissolved oxygen refers to oxygen dissolved in water. Its concentration is expressed as the amount of oxygen per unit volume and the unit is mg/L. Biologically, oxygen is an essential element for respiration of underwater life and also acts as a chemical oxidizer. The solubility of oxygen in water is affected by water temperature, salinity, barometric pressure, etc. and decreases as water temperature rises. Measurement of dissolved oxygen by the membrane electrode method The membrane electrode method measures a diffusion current or reduction current generated by the concentration of dissolved oxygen or partial pressure of oxygen to obtain the concentration of dissolved oxygen. This method is not affected by the pH value of water being measured, oxidation and reduction substances, color, turbidity, etc. and the measurement method offers good reproducibility. When a sensor is inserted into water, an air layer forms on the membrane (Teflon membrane). The ox...