4-20mA to Process Variable Formula

 This current to measurement conversion tool will convert an electrical signal within the range of 4 to 20 milliamps to the ideal reading of any linear measurement type and create an incremental milliamp conversion scale for each measurement range entered.


Formula

This tool uses the following formula to calculate the the measurement reading output from a current signal input over a 4-20mA range:


Measurement Rdg = Low Limit + (High Limit – Low Limit) x (mA out -4) / 16


Parameters

Current Loop Signal (4-20mA) Reading

Add the current loop signal reading in milliamps (mA) between 4 and 20 mA that you want to convert.


Measurement Unit

Enter the measurement unit associated with the output values.


Lowest Measurement

Add the minimum possible value for the measurement range of your instrument. For example zero would be a typical value for most instrumentation but you can also add negative (-) or positive (+) values as well. A value in any engineering units can be used as long as it relates to a linear measurement, and the same unit is used for the Highest value.


Highest Measurement

Add the maximum possible value for the measurement range of your instrument, e.g. full scale or full range. This value can be negative (-) or positive (+). Any engineering units can be used as long as it relates to a linear measurement, but the same unit must be used for the Lowest value.


Measurement Reading – Answer

This is the ideal converted measurement for your instrument and therefore represents a perfect reading excluding the measurement uncertainty error of your instrument. The answer value is displayed in the same engineering unit that you entered for the Lowest and Highest range points.


Help

Conversion precision

How precise is the converted measurement?

The linear measurement Answer is displayed to a precision of 9 significant figures.


Inverted signal

How do I convert an inverted or reversed 4-20mA signal?

Swap around the values you enter into the Lowest and Highest text boxes


Calibrating 4-20mA device

Can I use this converter to calibrate a 4-20mA measurement device?

You can partly use this converter to aid calibration. When you calibrate you will need to precisely measure both the input and output parameter. You can use this converter to determine the ideal measurement reading and compare it with the calibration measurement to determine the calibration error.


Input or output 4-20mA

Do I enter the input or the output value for the 4-20mA signal?

This converter is not input or output specific, so you can convert either ‘input to output’ or ‘output to input’.


Linear measurement

What is a linear measurement?

This means that if you were to plot input and output readings on a graph they would produce a straight line.

Comments

Popular posts from this blog

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

Thermowell Insertion and Immersion Length

 The thermowell is the industrial housing for temperature elements like RTD or thermocouple or temperature gauges. Thermowell is directly exposed to process fluid/media. Inside the thermowell, element/gauge is installed. Thermowell transfers the heat to the temperature element. Depending upon the element type, the fluid temperature can be known. So Thermowell protects the temperature element against harsh conditions and process fluid. It enables removal of the temperature element for replacement, repair, or testing without affecting the process system. Generally, thermowells are provided with all-temperature Elements like RTD or Thermocouple or temperature gauge. A few exceptions would be bearing RTD, skin type thermocouple, air duct thermometer, etc where thermowell is not applicable / required. When the thermowell assembly is inserted into the pipe, it is subjected to vibration. This vibration is caused by vortices to be generated alternately on either side of the thermowell. The...